From the 2018 UPC Illustrated Training Manual, Chapter 5, WATER HEATERS

507.2 Seismic Provisions. In seismic design categories C, D, E, and F, water heaters shall be anchored or strapped to resist horizontal displacement due to earthquake motion. Strapping shall be at points within the upper one-third and lower one-third of its vertical dimensions. At the lower point, a distance of not less than 4 inches (102 mm) shall be maintained from the controls with the strapping.

Seismic activity can cause the water heater to be displaced, creating a potentially dangerous condition. The gas connector may break (which could allow gas to flow freely into the space), or the vent connection may separate, allowing products of combustion to enter the space. Consideration must also be given to the possibility of a fire started by the water heater from damage to either the fuel-gas or electrical connections to the tank. In the event of a prolonged interruption of utilities, water heaters may provide an emergency source of drinking water, particularly if they are properly restrained and not destroyed during the earthquake. See Figure 507.13a for an example of water heater restraints.


We had a lot of interest last week with a posting regarding 2018 UPC ITM Section 905.2 titled "Horizontal Drainage Pipe".

Some of you caught the error for the Trap (Closet) Arm distance where the drawing showed a maximum of 5 feet but the code allows 6 feet (corrected version above). Thanks for calling us out on that.

There were also comments about whether the venting should be called horizontal or flat venting. Either term can be used but based on code definitions we think horizontal is preferred.

Lastly we were challenged about the illustration where the vent is attaching to the drain line and then runs horizontally.

Refer to UPC Section 905.3 Vent Pipe Rise. Unless prohibited by structural conditions, each vent shall rise vertically to a point not less than 6 inches above the flood-level rim of the fixture served before offsetting horizontally, and where two or more vent pipes converge...

There are conditions where exceptions are made to the general rule... and this is one of those exceptions.

The 2018 Uniform Plumbing Code Illustrated Training Manual is available for purchase here.


(This email is not to be considered the official position of IAPMO, nor is it an official interpretation of the Codes.)

© 2019 International Association of Plumbing and Mechanical Officials.

 
LinkedInLinkedInLinkedInLinkedInIAPMO website LinkedIn
 

You will continue to receive e-mail notifications from us until such time as you unsubscribe. To make sure these e-mails are not sent to your bulk or junk mail folders, add news@iapmo.org to your address book. Requests for new subscriptions or change of e-mail address should be sent to news@iapmo.org. IAPMO does not knowingly participate in SPAM. We do not sell, rent or trade the names on our e-mail list; your e-mail address is only used to send messages from IAPMO. If you wish to be removed from this list, follow the link below.

 

Facebooktwitteryoutubelinkedinlinkedin

Twitter LinkedIn